UNINTERRUPTIBLE POWER SUPPLY SYSTEM S3000 S4 Uninterruptible power supply system S3000 is designed to provide high quality power to telephone exchanges and other telecom devices, where low disturbances, low noise and short response time are mandatory. S3000 system is designed for 24 hours autonomous operation, enabling the application in remote locations without crew. May operate with or without batteries, with or without diesel generator or other auxiliary power source. Uninterruptible power supply system S3000 S4 is manufactured for 48V, 60V, 24V and 110V output voltage versions. Covers 20 kW to 45 kW output power range. S3000 S4 is easy to expand or modify "on line", without system interruption or degradation of basic functions. Features
Applications
Benefits
Power supply system S3000 is a modern, highly professional system, featuring exceptional electrical characteristics, simple handling and high reliability. Thanks to many adjustable and programable features, easily copes with customer special requests. Together with other GVS products, like switching systems, test & measurement equipment and other, S3000 system offers complete, well composed solution and forms one-stop-shop for all telecom equipment for your telecom network node. Exceptional resistance to mains voltage disturbances and high reliability make S3000 system an ideal solution for operation in harsh conditions, like rural areas. If You have an installation site where other power supply systems fail, S3000 is the right system for You. Power supply system S3000 is designed for international market and is available in english, russian and serbian language versions. Technical data Input data
Mains voltage Vi 220/230 Vac
Mains frequency 47-63 Hz
Mains voltage range -15 % .. +10 %
Mains distorsion 30 %
Power factor cos φ > 0,98
Input fuse per unit 10А
Input protection Input fuse fast 10 А
Overvoltage protection 253 .. 265 Veff
Undervoltage protection 176 .. 187 Veff
Voltage spike protection varistor
Fast overvoltage protection yes
Output data
Voltage regulation better than 1 %
Response time 1 msec
Overshoot @ Δ=50% ±5% Vnom
Turn on / turn off overshoot none
Voltage spikes < 2 Vp-p
Psophometric noise < 1 mVac
Noise 10Hz-450kHz < 25 mV
Wideband noise < 10 mVac/MHz
Current limit 105 %
Load fuses 2х400,8х250 Adc
Current sharing 5 %
Output protection
Output short-circuit yes
Short-circuit start-up yes
Batteries
Configuration dependent
General data
Operation & maintenance RS232, RS485
Temperature range 0 °C .. 40 °C
Storage temperature -10 °C .. 70 °C
Relative humidity 0 .. 90 %
Noise < 55 dB @ 1 m
Measure/display accuracy ±1 % , ±0,5 %
Service life 40 years
Spare parts 10 years
EMC ETSI EN 300 386
Dimensions
Height 1360 mm
Width 1320 mm
Depth 620 mm
Other protections and safety
Input/output insulation 2500 Veff
Input/ground insulation 2000 Veff
Output/ground insulation 500 Veff
Insulation resistance 1000 MΩ @ 500 Vdc
Ordering codes
▲▲ voltage 48: 48 Vdc, 60: 60 Vdc, 24: 24 Vdc, 110: 110 Vdc ◆◆ language SR: serbian, RU: russian, EN: english |